SERIES
500
|
|||||
| OPTIONS1 | OPTIONS2 | OPTIONS4 | |||
|
OPERATIONAL VARIATIONS |
|
| SERIES 510 |
AUTO RESET with Test and Accept facilities The alarm point automatically resets to the safe state when the input holding signal is re-applied following the alarm condition. |
| SERIES 530 |
MANUAL RESET with Test, Reset and Accept facilities The alarm point does not reset
automatically when the input holding signal is re-applied following the
alarm condition. |
| SERIES 540 |
AUTO RESET PLUS FLEETING ALARM RETENTION with Test and Accept facilities The alarm point automatically resets to the safe state when the holding signal is re-applied following an alarm condition, provided the alarm condition has been previously accepted by operation of the common ACCEPT pushbutton. |
|
MOUNTING VARIATIONS |
|
| 511, 531, 541 |
ENCLOSED SITE MOUNTED SYSTEMS These systems are in wall mounting
enclosures, available in IP42 or IP55 construction. Any number of alarm points, together with any optional variation, may be specified. The size of the enclosure will depend on the total number of alarm points required. |
| 512, 532, 542 |
ENCLOSED FRONT PANEL MOUNTING
MODULES Control Module
- (Link to Outline Drawing) Add-on Modules
- (Link to Outline Drawing) |
| 513, 533, 543 |
OPEN RACK REAR PANEL MOUNTING SYSTEM Designed for panel mounting applications where it is necessary to display the alarm indicators over a large area or within a mimic diagram. Any number and variation of alarm points may be provided with this form of mounting. |
|
OPTIONAL VARIATIONS (If no variations are required, specify the variation code as 00) |
|
| Code 00 |
No variation |
| Code 01 |
Individual direct-acting shutdown signal or signals. The shutdown signal is 0 during the alarm condition and at supply pressure in the safe condition. |
| Code 02 |
Individual reverse-acting shutdown signal or signals. The shutdown signal is at supply pressure during the alarm condition and 0 in the safe condition. This is not fail-safe. |
| Code 03 |
Group direct-acting shutdown signal. The shutdown signal is 0 if any point in the group of alarm points goes into the alarm condition, and is at supply pressure under the all-safe condition. |
| Code 04 |
Group reverse-acting shutdown signal. The shutdown signal is at supply pressure if any point in the group of alarm points goes into the alarm condition, and is 0 under the all-safe condition. This is not fail-safe. |
| Code 05 |
First-up fault indication. First-up alarm point flashes - other alarm points steady. After ACCEPT - all steady and first-up again available. |
| Code 06 |
Priority selection of alarm or alarm groups. |
| Code 07 |
Zone and group alarm systems. |
| Code 08 |
Remote alarm Accept facility. |
| Code 09 |
Variations not covered by standard optional listings. |
| With all the above optional variations it is necessary to detail if the variation is to be applied to the whole system, or to detail the alarm points which require the option. | |
|
| |